GREE Livo R32 18,000 Btu/h class

GREE rates this single-zone wall system for 18,000 Btu/h of cooling. It uses a 208/230 V supply and R-32 refrigerant.

Indoor unit
LIV18HP230V1R32AH
Outdoor unit
LIV18HP230V1R32AO

Cost and room performance

Equipment and ten years of electricity

$5,349.65

Listed equipment price
$2,332 3 retailers
Ten years of electricity
$3,017.65
Annual electricity use
1,676.5 kWh
Electricity assumptions$0.18/kWh · 10 million Btu cooling + 10 heating per year

Use the electricity rate from your bill. Enter the heat your room needs each year and the heat it needs removed in summer. A load estimate can supply those figures. The starting values are a shared example.

The estimate covers the equipment and its electricity at a constant rate. Budget separately for installation, backup heat and service.

Scores by criterion

Scores compare systems on each criterion. The best measured result earns 100 and the worst earns 0. N/A means a reading or score is unavailable. How scores are calculated

  • 10-year equipment + electricity $5,349.65
    59 / 100
  • Price per 1,000 Btu/h at 5°F $192.73
    55 / 100
  • Heat available at 5°F 12,100 Btu/h
    26 / 100
  • Electricity for 1 million Btu at 5°F 158.4 kWh
    16 / 100
  • Minimum heat at 47°F N/A
    N/A
  • Minimum cooling at 95°F N/A
    N/A
  • Indoor sound, lowest fan 34 dB(A)
    17 / 100
  • Indoor sound, highest fan 53 dB(A)
    7 / 100
  • Electricity for 1 million Btu of cooling 50 kWh
    29 / 100
  • Electricity for 1 million Btu of heat 117.6 kWh
    13 / 100
  • Equipment price $2,332.00
    63 / 100
  • Heat retained at 5°F 71.2%
    13 / 100
  • Seasonal cooling efficiency 20 SEER2
    17 / 100
  • Earlier weighted value score 108.4 (size-class reference of 100)
    30 / 100

Electricity per million Btu

Cooling
50 kWh
Heating · Region IV rating
117.6 kWh

Compare models doing the same amount of heating or cooling. A lower number uses less electricity.

What your equipment budget buys at 5°F

Equipment price per 1,000 Btu/h at 5°F
$192.73
Heat available at 5°F
12,100 Btu/h
COP at 5°F
1.85
Electricity per million Btu at 5°F
158.4 kWh

EPA record for this pair. Compare heating output with your room’s heat loss at the same outdoor temperature. COP measures heat delivered per unit of electricity at that temperature.

How low can the compressor run?

Minimum heating output at 47°F
N/A
Minimum cooling output at 95°F
N/A

Below the minimum steady output at that outdoor temperature, the system may cycle on and off to meet a lighter load.

Indoor sound across fan speeds

Cooling sound range
34–53 dB(A)

The range runs from the quietest to the highest published indoor fan setting in cooling mode. Compare fan settings for a bedroom.

Formulas and ranking rules

Equipment price & installation

Average equipment price
$2,332
3 retailers · $2,163 to $2,670 · Price sources reviewed

Prices cover the listed equipment package. Installation, tax and shipping are separate.

What would the whole job cost?

Ask for an estimate for the LIV18HP230V1R32AH and LIV18HP230V1R32AO, including labor, refrigerant lines and electrical work.

Call for an installation quote(833) 246-4401
Equipment price sources
  • HVACDirectIndoor unit $712 + outdoor unit $1,451
    $2,163
  • SupplyHouse
    $2,163
  • PTAC Direct
    $2,670

What an installation quote covers

The median equipment price in the 18,000 Btu/h class is $3,099.75 (18 of 18 systems priced).

Earlier price and efficiency score

Weighted score 108.4. The reference for the 18,000 Btu/h class is 100.

Efficiency-only benchmark 92.

Weights and same-size benchmarks

Published specifications

Cooling
Rated cooling capacity18,000 Btu/h
Published minimum · outdoor temperature unspecified3,753 Btu/h
Published maximum · outdoor temperature unspecified20,300 Btu/h
Seasonal efficiency (SEER2)20 Btu/Wh
Efficiency at the rating point (EER2)12.35 Btu/Wh
Moisture removal3.8 US pt/h
Lower published outdoor operating limit0 °F
Upper published outdoor operating limit118 °F
Heating
Seasonal efficiency (HSPF2, Region IV)8.5 Btu/Wh
Rated output at 47°F19,100 Btu/h
Maximum output at 47°F22,838 Btu/h
Rated output at 17°F15,300 Btu/h
Maximum output at 17°F14,749 Btu/h
Rated output at 5°F12,100 Btu/h
Maximum output at 5°F12,411 Btu/h
Published minimum · outdoor temperature unspecified2,730 Btu/h
Published maximum · outdoor temperature unspecified22,500 Btu/h
COP at 5°F · rated output1.75
COP at 5°F · maximum output2.07
Power at 5°F · maximum output1,759 W
Lower published outdoor operating limit-13 °F
Upper published outdoor operating limit75 °F
Sound levels
Indoor, cooling · quietest setting34 dB(A)
Indoor, cooling · highest published level53 dB(A)
Indoor cooling fan stages · published order53 / 49 / 46 / 44 / 42 / 38 / 34 dB(A)
Outdoor · operating mode unspecified57 dB(A)
Installation details
Power supply208–230 V / 1 Ph / 60 Hz
RefrigerantR-32
Minimum circuit ampacity13 A
Maximum overcurrent protection15 A
Maximum line-set length82 ft
Maximum vertical separation33 ft
Warranty
Standard parts coverage5 years
Standard compressor coverage7 years

A qualifying GREE Select installation and registration can extend coverage to 10 years. The linked warranty program lists the conditions.

Reference calculations against fixed benchmarks

The electricity benchmarks use 18 SEER2, 12 EER2 and 9 HSPF2 at the same useful load. A negative saving means higher modeled consumption. Reference formulas

Seasonal cooling electricity savings10.0%
Cooling input reduction at the EER2 test point2.8%
Seasonal heating electricity savings-5.9%
Electricity savings with equal heating and cooling loads-0.6%
Heat at 5°F as a share of rated heat at 47°F71.2%
Cooling turndown below rated capacity at 95°FN/A
Quietest cooling mode below a 30 dB(A) reference-4 dB(A)

ENERGY STAR cross-check

The ENERGY STAR listing names both units on this sheet.

ENERGY STAR ID4515362
AHRI reference214780395
Cold Climate designationYes
Rated cooling18,000 Btu/h
Heating at 47°F17,000 Btu/h
Heating at 17°F15,300 Btu/h
Heating at 5°F12,100 Btu/h
COP at 5°F1.85
SEER220 Btu/Wh
EER212 Btu/Wh
HSPF28.5 Btu/Wh
5°F output as a share of 47°F rated output71.18%

Reading the sources

The model sheet and the ENERGY STAR listing give different values. The catalog uses the equipment document for cooling capacity and efficiency.

MeasurementEquipment documentENERGY STAR
EER212.3512
Rated heat at 47°F (Btu/h)19,10017,000

GREE’s extended heating tables use full output with a 70°F indoor dry-bulb temperature. The system submittal reports rated output separately.