Read the Btu/h at a stated temperature
Both systems below are rated for 12,000 Btu/h of cooling. At 5°F outdoors, ENERGY STAR lists 11,500 Btu/h of heat for the ACiQ pair and 10,100 Btu/h for the Mitsubishi GX model family. The ACiQ record names both units exactly. The Mitsubishi record uses model-number patterns that cover the GX12 shown here. You can check those patterns in the GX12 equipment record.

Mitsubishi Electric GX Premier
10,100 ÷ 14,400 = 70.1% retained
ACiQ Platinum Extreme Heat
ACIQ-12W-HH-MD / ACIQ-12ZPL-HP230C
11,500 ÷ 12,000 = 95.8% retained
Use the percentage to answer a second question
Capacity retention tells you how much of each system’s own 47°F heating rating it keeps at 5°F. Model families may have different 47°F ratings even when their nominal cooling sizes match. The Btu/h figure is the one to compare with the room’s heating load at the same temperature.
Consider the 18,000 Btu/h GREE Sapphire and Daikin Aurora. The Sapphire has the higher seasonal heating efficiency rating. At 5°F, the listed heating output is higher for the Aurora model family. Which number matters depends on whether you’re estimating a winter bill or checking the room’s heat supply on a cold night.
Ask for the number at your winter design temperature
If your local winter design temperature is below 5°F, ask for a manufacturer’s performance table covering that temperature and a room-by-room heat loss calculation. An operating limit of −13°F, for example, tells you the compressor can run that cold. To decide whether you’ll need backup heat, you still need its output there in Btu/h.