How much heat does a mini-split deliver at 5°F?

Check the heating capacity at 5°F in Btu/h against your room’s heat loss. Two systems with the same cooling rating show why the heating figure matters.

Read the Btu/h at a stated temperature

Both systems below are rated for 12,000 Btu/h of cooling. At 5°F outdoors, ENERGY STAR lists 11,500 Btu/h of heat for the ACiQ pair and 10,100 Btu/h for the Mitsubishi GX model family. The ACiQ record names both units exactly. The Mitsubishi record uses model-number patterns that cover the GX12 shown here. You can check those patterns in the GX12 equipment record.

A single-fan outdoor heat pump is elevated above the ground beside a house.
The unit here stands on blocks above mud and runoff. In snow country, ask the installer to account for expected snow accumulation and drainage during defrost.Martha Rose Construction · Courtesy of the U.S. Department of Energy. Image source

Mitsubishi Electric GX Premier

MSZ-GX12NL / MUZ-GX12NL

At 47°F, rated14,400 Btu/h
At 5°F10,100 Btu/h

10,100 ÷ 14,400 = 70.1% retained

ACiQ Platinum Extreme Heat

ACIQ-12W-HH-MD / ACIQ-12ZPL-HP230C

At 47°F, rated12,000 Btu/h
At 5°F11,500 Btu/h

11,500 ÷ 12,000 = 95.8% retained

Both panels use the same scale. The upper bar shows the 47°F reference. The lower bar shows the 5°F reading.

Use the percentage to answer a second question

Capacity retention tells you how much of each system’s own 47°F heating rating it keeps at 5°F. Model families may have different 47°F ratings even when their nominal cooling sizes match. The Btu/h figure is the one to compare with the room’s heating load at the same temperature.

Consider the 18,000 Btu/h GREE Sapphire and Daikin Aurora. The Sapphire has the higher seasonal heating efficiency rating. At 5°F, the listed heating output is higher for the Aurora model family. Which number matters depends on whether you’re estimating a winter bill or checking the room’s heat supply on a cold night.

Ask for the number at your winter design temperature

If your local winter design temperature is below 5°F, ask for a manufacturer’s performance table covering that temperature and a room-by-room heat loss calculation. An operating limit of −13°F, for example, tells you the compressor can run that cold. To decide whether you’ll need backup heat, you still need its output there in Btu/h.